The Alumavent 3960/3961/3965/3967 insulated, extruded aluminum control damper features a true thermal-break blade design and is suitable for use in low to medium velocity and pressure exhaust or intake applications. The standard co-extruded santoprene blade and jamb seals provide ultra low leakage characteristics. Optional ELT silicone seals and thermally-broken frame provide maximum performance for extreme low temperature applications. The 3960/3961/3965/3967 is available in both opposed and parallel blade configurations.
Depth Blades Closed: | 4" (101 mm) |
Depth Blades Open: | 6 1/8" (156 mm) max. |
Material: | 0.081" (2.06 mm) |
Blade Style: | 3960-OB Opposed Blade, 3960-PB Parallel Blade |
Blade Thickness: | 0.081" (2.06 mm) |
Bearings: | Dual bearing system, engineered thermoplastic |
Seals: | Co-extruded santoprene blade seal and jamb seals |
Axles: | 3/8" Aluminum Square Bar |
Frame Style: | 3960 and 3961 In-Duct Mount / 3965 Flange-to-Duct Mount / 3967 Front Flange |
Blade Insulation: | Blades are thermally broken. High density polyurethane non-CFC foam (R-2.25) |
Minimum Height: | 8" (203 mm) Single Blade - 15" (381 mm) Multiple Blade |
Maximum Panel Width: | 48" (1219 mm) |
Maximum Panel Height: | 60" (1524 mm) |
Maximum Panel Size: | 20 sq. ft. |
Leakage: | Does not exceed 7 CFM/ft² (34l/s/m²) against 4" w.g. (1 kPa) differential static pressure at -40° F (-40° C) |
Linkage: | Concealed in Frame |
Standard Finish: | Mill |
Standard Motor Installation: | Side shaft direct drive, extendable up to 12" |
Operating Temperature Range: | -40º to +200º F |