53CVD 3 HOUR LABEL DYNAMIC FIRE DAMPER is suitablefor use in vertical fire separations with a fire resistance rating of 4 hours or less, and is UL/ULC approved for use in HVAC systems where the fans remain on in the event of a fire.
DEPTH: 4 ¼“ (108).
FRAME: Roll formed 20 Ga. galvanized steel with hemmed edge.
BLADES: Roll formed 22 Ga. galvanized steel.
Interlocking curtain type blades.
FUSIBLE LINK: 165°F (74 C).
OPTIONAL CONSTRUCTION